Pull Out Tests for CINTEC Anchors carried out on the
|
|
|
The CINTEC Anchors were installed on December 8th, 1994 at the 6th floor elevation by David Aston from CLS CINTEC America in the presence of Mr. R. Wagner LZA Technology and Mr. A. Destefano of
Empire National. 1/2" Ø RAC anchors were used being of different lengths.
|
| Type 1 overall length 3 3/4" socked 2 3/4" for testing in 4" thick limestone panels.
Type 2 overall length 7 3/4" socked 6 3/4" for testing in 8" thick limestone panels. Type 3 overall length 11 3/4" socked from the rear for testing the brick back up wall.
|
|
| Testing was carried out 8 days after installation by David Aston, in the presence of Mr. R. Wagner using a Mark IV Hilti Test Meter Serial No. 01632.
The loads achieved are set out on the test date result sheet overleaf. It should be noted at the achieved loads there were no failures or any visible damage to the areas surrounding the test anchors. |
|
COMPANY ADDRESS |
TEST ANCHORS & RESULTS Date: 16/12/1994 |
SITE ADDRESS |
| LZA TECHNOLOGY 641 AVENUE OF THE AMERICAS NEW YORK NY 10011 |
EMPIRE STATE BUILDING 5TH AVENUE NEW YORK |
| TEST REQUIRED | TEST NO | INSTALL TIME | TYPE OF ANCHOR | LOAD REQUIRED | LOAD ACHEIVED | BASE MATERIAL | STOCK IMBEDMENT | STOCK DIAMETER | PULLOUT TIME |
| 1) To Test Brick Facade 2) To Secure Brick Facade on 6th Floor |
1 2 3 4 5 |
20 mm 20 mm 20 mm 20 mm 20 mm |
3/8" Solid Bar 3/8" Solid Bar 3/8" Solid Bar 3/8" Solid Bar 3/8" Solid Bar |
1000lbs 1000lbs 1000lbs 1000lbs 1000lbs |
3200lbs 2800lbs 3200lbs 3150lbs 3000lbs |
STONE STONE STONE BRICK BRICK |
2 3/4" 2 3/4" 6 3/4" 6" 6" |
1" 1" 1" 1" 1" |
10 MINS 10 MINS 15 MINS 10 MINS 10 MINS |
PERSONS PRESENT ON TEST / DEMONSTRATION
| PRINT NAME | COMPANY | POSITION | PHONE NUMBER |
| MR ROBERT WAGNER | LZA TECHNOLOGY | SENIOR PROJECT DIRECTOR | 212 741 1300 |
COMMENTS
It should be noted that at the achieved loads no failure of the anchors was observed, in addition, there was no visible damage to the areas surrounding the test anchors.
| SIGNED ROBERT LLOYD-REES FOR & ON BEHALF OF CAVITY LOCK SYSTEMS LTD POSITION:- CLS NORTH AMERICA |
CLS CINTEC CANADA LTD. |
SIGNED ROBERT WAGNER FOR & ON BEHALF OF LZA TECHNOLOGY POSITION:- SENIOR PROJECT DIRECTOR |