  Building Research Establishment
Carston    Watford    WD2 7JR
Telephone 0923 894040    Telex 923220    Fax 0923 664010
Direct line 0923 66
GTN 3532
Mr. J. Dymmock
Cavity Lock Systems
Factory Road
Newport
Gwent
NP9 5FA
your reference    
our reference   BRE/67/50/1
date   23/11/93
 
Sent by FAX to:  0633 246110

 

Dear John,

Fire testing of Cavity Lock remedial cavity wall tie.

In the latest test in our fire test rig with a static dead load on each tie of 1.3kN your tie survived a two hour test without failure of any of the three replicate samples.

All three samples are now placed in the upper half of the wall and would have reached several hundred degrees in the part of the tie nearest the fire face.

This indicates that this tie system can, when installed using the correct techniques, be recommended for repair work to buildings having a fire period requirement of up to 2hrs.

Yours sincerely

 

 

R.C. de Vekey

Head of Masonry Structures Section, Structural Design Division, Geotechnics and Structures Group